Product Details:
Payment & Shipping Terms:
|
Voltage Rating (Uo/U): | 450/750V | Operating Temperature: | -25°C To +90°C |
---|---|---|---|
Minimum Bending Radius: | Fixed: 3 X Overall Diameter Flexed: 6 X Overall Diameter | Sheath Colour: | White |
Conductor: | Class 5 Flexible Copper Conductor | Separator: | Mica/glass Fire Barrier Tape |
Insulation: | LSZH (Low Smoke Zero Halogen) | Sheath: | LSZH (Low Smoke Zero Halogen) |
Highlight: | fire proof cable,fire retardant cable |
BS 5266-1 Standard Fire Resistance Cable for Normal Emergency Lighting
APPLICATION
A fire resistant, flexible LSZH (Low Smoke Zero Halogen) cable suitable for normal emergency lighting, fire alarms and voice alarm systems.
CABLE STANDARDS
BS 5266-1, 8.2.2(b) and (d) Emergency lighting, BS 8434-2,
BS 5839-8, BS 5839-1, 26.2e
BS EN 50200 - PH30, PH60, PH120 BS 6387 C W and Z
LUL 1-085, IEC 331-3, 120 mins in conduit
DIMENSIONS
UNI-Cables PART NO. |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
UNIFR03015 | 3 | 1.5 | 10 | 135 |
UNIFR03025 | 3 | 2.5 | 11.2 | 168 |
UNIFR04015 | 4 | 1.5 | 11.2 | 149 |
UNIFR04025 | 4 | 2.5 | 12.4 | 211 |
CONDUCTOR
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km |
1.5 | 13.3 |
2.5 | 7.98 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NOMINAL CROSS SECTIONAL AREA mm² |
CURRENT RATING (CLIPPED DIRECT) | |
Single Phase AC or DC Amps |
Three Phase AC Amps |
|
1.5 | 23 | 21 |
2.5 | 31 | 28.5 |
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
DC mV/A/M |
SINGLE PHASE AC mV/A/m |
THREE PHASE AC mV/A/m |
1.5 | 34.1 | 34 | 29.7 |
2.5 | 20.9 | 21 | 17.6 |
Contact Person: achi